1002-909

Additional Information

Electrical Test Equipment - 15kV Insulation Tester - Megger - MIT1525 US 15kV Insulation Tester - 1002-909 - MIT1525-US Insulation Tester 15kV IRT, IR, IR(t), DAR, PI, DD, SV, Ramp, USB, US plug

Megger MIT1525 Insulation Resistance TesterMegger’s range of MIT insulation resistance testers are targeted at original equipment manufacturers and industrial companies. The top of the new range Megger MIT1525 performs insulation resistance tests up to 15 kV with a 30 T-ohm maximum resistance and an accuracy of ±5 % from 1 M-ohm up to 3 T-ohmAn intuitive user interface ensures no lost time remembering how to use the tester. Simplicity of operation is achieved with two rotary
switches and the large backlight display which enables multiple results to be displayed simultaneously. A graphical quick start guide is provided inside the lid to assist first time users.The MIT range share dual case design which includes a tough outer case to protect the tester from knocks/drops and an inner fire retardant case. The IP rating is IP 65 case closed eliminating moisture and dust ingress.

*Ships with free calibration certificate! 

Features:
  • Insulation resistance up to 30 T-ohm @ 15 kV, 20 T-ohm @ 10kV,10 T-ohm @ 5 kV
  • IR, Timed IR, DAR, PI, DD, SV and ramp diagnostic tests
  • High current – 3 mA short circuit current
  • High noise immunity – 3mA (5kV and 10kV) 6mA (15kV)
    of noise rejection
  • Li-ion battery – up to 6 hrs continuous testing @ 5 kV with a 100M load, battery meets IEC 62133
  • Safety rating: CATIV 600 V to 3000 m (5 kV, 10 kV), CATIV 1000 V to 3000 m (15 kV)
  • Large LCD display with backlight
  • Dedicated voltmeter function (30 V to 660 V)
  • Advanced memory, on screen recall and real time clock for date/time stamped results
  • Download of on-board results via USB interface
  • PowerDB Lite asset management software
  • Recorded temperature (measured by independent instruments) can be saved with test result
  • PowerDB Lite asset management software supplied
Application:
  • The Insulation Resistance (IR) test is a quantitative test which
    indicates the effectiveness of a product’s electrical insulation.
    Applications include cables, transformers, motors/generators,
    circuit breakers and bushings. Common insulation tests
    are the “spot test�, a 1 minute IR test and a 10 minute
    Polarisation Index (PI) test, where PI is the ratio R10min/R1min and
    temperature independent.