ABB
1SDA054403R1T5N 630 PR222DS/P-LSIG In=630 4p F F
T5N 630 PR222DS/P-LSIG In=630 4p F F
Moulded / Molded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax T (IEC) series) - T5N 630 PR222DS/P-LSIG In=630 4p F F - 4-poles (4P4d) - Rated current 630A - Short circuit breaking capacity (Icu) 36kA (415Vac) - Electronic (PR222DS/P-LSIG) trip unit - equivalent to T5N630PR222DSPLSIGIn6304pFF
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Brand
SKU
1SDA054403R1
Please add this item to cart to request a quote.
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Click on the colored tile to view a product selector for this product series:
1SDA054403R1ABB - Tmax T
Description
Moulded / Molded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax T (IEC) series) - T5N 630 PR222DS/P-LSIG In=630 4p F F - 4-poles (4P4d) - Rated current 630A - Short circuit breaking capacity (Icu) 36kA (415Vac) - Electronic (PR222DS/P-LSIG) trip unit - equivalent to T5N630PR222DSPLSIGIn6304pFF
Specifications
Primary brand
ABB
Secondary brand
SACE
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Tmax T (IEC)
Sub-range name
T5N complete breakers
Functions
Moulded / Molded Case Circuit Breaker (MCCB)
Protection parameters set (available via Modbus)
Protections (L/S/I/G) (available via Modbus)
Failed tripping under fault conditions (available via Modbus)
Protection parameters set (available via Modbus)
Protections (L/S/I/G) (available via Modbus)
Failed tripping under fault conditions (available via Modbus)
Poles
4-poles (4P4d)
Rated current
630A
Trip current rating
630 AT
Frame current rating
630 AF
Rated operating voltage (Ue)
690 V
Rated Voltage (DC)
750Vdc
Rated voltage (AC)
690Vac
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
1000 V
Connection type
Ring-lug or bar connections
Ultimate short circuit current breaking capacity (Icu)
70kA (240Vac)
36kA (380Vac)
36kA (415Vac)
30kA (440Vac)
25kA (500Vac)
20kA (690Vac)
36kA (250Vdc; 2 poles in series)
25kA (250Vdc; 3-poles in series)
16kA (500Vdc; 3-poles in series)
36kA (380Vac)
36kA (415Vac)
30kA (440Vac)
25kA (500Vac)
20kA (690Vac)
36kA (250Vdc; 2 poles in series)
25kA (250Vdc; 3-poles in series)
16kA (500Vdc; 3-poles in series)
Short circuit withstand current (Icw)
5kA (1s)
Service short circuit current breaking capacity (Ics)
70kA (240Vac)
36kA (380Vac)
36kA (415Vac)
30kA (440Vac)
25kA (500Vac)
20kA (690Vac)
36kA (380Vac)
36kA (415Vac)
30kA (440Vac)
25kA (500Vac)
20kA (690Vac)
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
(415Vac) 100 %
Trip unit type
Electronic
PR222DS/P-LSIG
LSIG
Display = none
PR222DS/P-LSIG
LSIG
Display = none
Protection functions
(L) Protection against overload
(S) Protection against short-circuit with time delay
(I) Instantaneous protection against short-circuit
(G) Protection against earth fault
(S) Protection against short-circuit with time delay
(I) Instantaneous protection against short-circuit
(G) Protection against earth fault
Protection settings
L - Protection against overload -- adjustable 0.4...1 x In (252A...630A)
S - Protection against short-circuit with time delay -- adjustable 0.6...10 x In (378A...6300A); with adjustable time trip curve
I - Instantaneous protection against short-circuit -- adjustable 1.5...12 x In (945A...7560A)
G - Protection against earth fault -- adjustable 0.2...1 x In (0.1...0.8s time delay)
S - Protection against short-circuit with time delay -- adjustable 0.6...10 x In (378A...6300A); with adjustable time trip curve
I - Instantaneous protection against short-circuit -- adjustable 1.5...12 x In (945A...7560A)
G - Protection against earth fault -- adjustable 0.2...1 x In (0.1...0.8s time delay)
Measurement function
Phase currents
Neutral current
Ground current
Neutral current
Ground current
Operating mode
Toggle
Dimensions
H205mm x W186mm x D103.5mm
Electrical durability (with load)
5000 operations
Mechanical durability (at no load)
20000 operations
Power dissipation/losses
(1-pole) 41 W
Order code / Manufacturer SKU
T5N 630 PR222DS/P-LSIG In=630 4p F F
1SDA054403R1
1SDA054403R1
Manufacturer product status
Commercialized
Equivalent to
T5N630PR222DSPLSIGIn6304pFF
EAN code
8015644555016
UPC code
662019389387
UNSPSC code
39121616
Compliant with standard(s)
IEC 60947-2
EC directive "Low Voltage Directives" (LVD) no. 2006/95/CE (in replacement of 73/23/ CEE and subsequent amendments)
EC directive "Electromagnetic Compatibility Directive" (EMC) 2004/108/CE
IEC 60073
IEC 60417-2
IEC 60529
IEC 60068-2-30 (tropicalization)
IEC 60068-2-6 (resistance to shocks and vibrations)
IEC 60068-2-27 (resistance to shocks)
EC directive "Low Voltage Directives" (LVD) no. 2006/95/CE (in replacement of 73/23/ CEE and subsequent amendments)
EC directive "Electromagnetic Compatibility Directive" (EMC) 2004/108/CE
IEC 60073
IEC 60417-2
IEC 60529
IEC 60068-2-30 (tropicalization)
IEC 60068-2-6 (resistance to shocks and vibrations)
IEC 60068-2-27 (resistance to shocks)
Related Documents
Name | Last Update | Language |
---|---|---|
ABB - Tmax T Moulded Case Circuit Breakers - Catalogue.pdf | 02 Feb 2023 | English (US) |