Schneider Electric
BMXCPS4002HPower supply module X80 - 100-240Vac - for severe environments
Power supply module X80 - 100-240Vac - for severe environments
Ruggedized power supply unit (PSU) - Redundant HSBY (Hot Standby) - for severe environments (with conformal coating) - Schneider Electric / Modicon (Modicon X80 series) - Rated power 40W - Supply voltage 85-264Vac (100-240Vac nom.) - backplane / rack mounting - IP20 - Rated for -13...+158°F / -25...+70°C ambient - replaces 140CPS12420C / 140CPS52400C / TSXPSY8500MC
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Brand
SKU
BMXCPS4002H
Online Price
$2,000.00
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Schneider Electric - Modicon X80 power supply unitsBMXCPS4002H
Description
Ruggedized power supply unit (PSU) - Redundant HSBY (Hot Standby) - for severe environments (with conformal coating) - Schneider Electric / Modicon (Modicon X80 series) - Rated power 40W - Supply voltage 85-264Vac (100-240Vac nom.) - backplane / rack mounting - IP20 - Rated for -13...+158°F / -25...+70°C ambient - replaces 140CPS12420C / 140CPS52400C / TSXPSY8500MC
Specifications
Primary brand
Schneider Electric
Secondary brand
Modicon
Main function
Power supply unit
Product series / family name
Modicon X80
Sub-range name
Modicon X80 power supply units
Functions
Ruggedized power supply unit (PSU)
Design
Redundant HSBY (Hot Standby)
for severe environments (with conformal coating)
for severe environments (with conformal coating)
Supply voltage (AC)
85-264Vac (100-240Vac nom.)
Rated power
40W
40W (24Vdc at -13...+158°F (-25...+70°C) I/O module power supply and processor if 3.3Vdc not loaded)
18W (3.3Vdc at -13...+158°F (-25...+70°C) I/O module logic power supply)
40W (24Vdc at -13...+158°F (-25...+70°C) I/O module power supply and processor if 3.3Vdc not loaded)
18W (3.3Vdc at -13...+158°F (-25...+70°C) I/O module logic power supply)
Protection functions
internal fuse not accessible primary circuit
overload protection secondary circuit
overvoltage protection secondary circuit
short-circuit protection secondary circuit
overload protection secondary circuit
overvoltage protection secondary circuit
short-circuit protection secondary circuit
Mounting mode
backplane / rack mounting
Degree of protection
IP20
Ambient air temperature for operation
-13...+158°F / -25...+70 °C
Ambient air temperature for storage
-40...+185°F / -40...+85 °C
Humidity
5-95% (at 131°F (55°C) without condensation)
Chemical resistance
IEC/EN 60721-3-3 -- class 3C1; 3C2; 3C3; 3C4 (Concentrations H2S 9900PPB (parts per billion) /SO2 4800PPB / Cl2 200PPB)
IEC/EN 60068-2-52 -- salt mist Kb test severity level 2 (3 x 24-hour cycles; 5% NaCl 40°C/104°F; relative humidity 93%)
ISA S71.04 -- classes G1 to Gx concentrations (H2S 60PPB / SO2 350PPB / Cl2 1450PPB / NO2 12PPB)
Gas resistant class Gx ISA S71.04
Gas resistant class 3C4 IEC 60721-3-3
Dust resistant class 3S4 IEC 60721-3-3
Sand resistant class 3S4 IEC 60721-3-3
Salt resistant level 2 IEC 68252
Mold growth resistant class 3B2 IEC 60721-3-3
Fungal spore resistant class 3B2 IEC 60721-3-3
Resistant to harsh environment (conformal coated PCB)
IEC/EN 60068-2-52 -- salt mist Kb test severity level 2 (3 x 24-hour cycles; 5% NaCl 40°C/104°F; relative humidity 93%)
ISA S71.04 -- classes G1 to Gx concentrations (H2S 60PPB / SO2 350PPB / Cl2 1450PPB / NO2 12PPB)
Gas resistant class Gx ISA S71.04
Gas resistant class 3C4 IEC 60721-3-3
Dust resistant class 3S4 IEC 60721-3-3
Sand resistant class 3S4 IEC 60721-3-3
Salt resistant level 2 IEC 68252
Mold growth resistant class 3B2 IEC 60721-3-3
Fungal spore resistant class 3B2 IEC 60721-3-3
Resistant to harsh environment (conformal coated PCB)
Thermal resistance
Change of temperature (with power ON) IEC 60068-2-14 (Nb) -- -25°C...+70°C/-13°F...+158°F; 5 cycles; t = 6hrs + 6hrs
Change of temperature (thermal shocks) (with power OFF) IEC/EN 61131-2; IEC 60068-2-14 (Na) -- -40°C...+85°C/-40°F...+185°F; 5 cycles; t = 3hrs + 3hrs
Change of temperature (thermal shocks) (with power OFF) IEC/EN 61131-2; IEC 60068-2-14 (Na) -- -40°C...+85°C/-40°F...+185°F; 5 cycles; t = 3hrs + 3hrs
Climatic resistance
Dry heat immunity (with power ON) IEC 60068-2-2 (Bb & Bd) -- 70°C/158°F; 16hrs and IACS E10 (70°C/140°F; 16hrs)
Cold immunity (with power ON) IEC 60068-2-1 (Ab & Ad) and IACS E10 -- 0°C...-25°C/32°F...-13°F; 16hrs + power on at -25°C/-13°F
Dry heat withstand (with power OFF) IEC/EN 61131-2; IEC 60068-2-2 (Bb & Bd) -- 85°C/185°F 96hrs
Cold withstand (with power OFF) IEC/EN 61131-2; IEC 60068-2-1 (Ab & Ad) -- -40°C/-40°F 96hrs
Cold immunity (with power ON) IEC 60068-2-1 (Ab & Ad) and IACS E10 -- 0°C...-25°C/32°F...-13°F; 16hrs + power on at -25°C/-13°F
Dry heat withstand (with power OFF) IEC/EN 61131-2; IEC 60068-2-2 (Bb & Bd) -- 85°C/185°F 96hrs
Cold withstand (with power OFF) IEC/EN 61131-2; IEC 60068-2-1 (Ab & Ad) -- -40°C/-40°F 96hrs
Technical compatibility with
Modicon M340 PLCs
Rated apparent power (S)
0.07kVA
Power dissipation/losses
8.5 W
Order code / Manufacturer SKU
BMXCPS4002H
Manufacturer product status
Commercialized
Replaces
140CPS12420C
140CPS52400C
TSXPSY8500MC
140CPS52400C
TSXPSY8500MC
Compliant with standard(s)
CSA C22.2 No.61010-2-201
EN61131-2EN/IEC 61010-2-201
EN/IEC 61000-6-5
EN/IEC 61850-3
UL61010-2-201
IACS E10
RoHS directive 2011/65/EU
WEEE directive 2012/19/EU
CE
EAC
Merchant Navy
REACH regulations (EC No. 1907/2006)
For USA and Canada -- Hazardous location class I; division 2; groups A;B;C; and D
For European Union -- ATEX for atmosphere Zone 2 (gas) and Zone 22 (dust)
For United Kingdom -- UKEX for atmosphere Zone 2 (gas) and Zone 22 (dust)
For other countries -- IECEx for atmosphere Zone 2 (gas) and/or Zone 22 (dust)
Meets or exceeds IEC60068-2 requirements -- Shocks 30g (vs IEC requirement 15g) / vibrations 3g (vs IEC requirement 1g)
EN61131-2EN/IEC 61010-2-201
EN/IEC 61000-6-5
EN/IEC 61850-3
UL61010-2-201
IACS E10
RoHS directive 2011/65/EU
WEEE directive 2012/19/EU
CE
EAC
Merchant Navy
REACH regulations (EC No. 1907/2006)
For USA and Canada -- Hazardous location class I; division 2; groups A;B;C; and D
For European Union -- ATEX for atmosphere Zone 2 (gas) and Zone 22 (dust)
For United Kingdom -- UKEX for atmosphere Zone 2 (gas) and Zone 22 (dust)
For other countries -- IECEx for atmosphere Zone 2 (gas) and/or Zone 22 (dust)
Meets or exceeds IEC60068-2 requirements -- Shocks 30g (vs IEC requirement 15g) / vibrations 3g (vs IEC requirement 1g)
Benefits
The Modicon X80 module platform features the latest I/O technology -- making it extremely compact
It has smaller cabinet dimensions with up to 64 discrete I/O for some modules
High density
Modicon X80 modules serve as the common in-rack I/O / expert and communication modules for Modicon M580 and Modicon M340 PAC platforms
This range also includes power supplies / racks and accessories common to both ranges
This module platform is available in single-rack or multi-rack configuration
It has smaller cabinet dimensions with up to 64 discrete I/O for some modules
High density
Modicon X80 modules serve as the common in-rack I/O / expert and communication modules for Modicon M580 and Modicon M340 PAC platforms
This range also includes power supplies / racks and accessories common to both ranges
This module platform is available in single-rack or multi-rack configuration
Location of origin
Indonesia (ID)
Related Documents
Name | Last Update | Language |
---|---|---|
Download official PDF datasheet for BMXCPS4002H from Schneider Electric | 18 Jun 2021 | English (US) |
Schneider Electric - Modules platform - Modicon X80 - Catalog.pdf | 08 Jan 2023 | English (US) |