PULS
CS10.244
AC/DC Power supply unit (PSU) / converter - 20% power reserve - PULS (DIMENSION C-Line series) - 10A (at 24Vdc; ambient less than 60°C) - 24Vdc-28Vdc (adjustable) / 12A / 240W output - with screw-clamp connections - Single-phase (1AC) input (180Vac-264Vac (200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz)) - DIN rail mounting (60mm width) - equivalent to #CS10244
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Brand
SKU
CS10.244
Online Price
$284.00
Discount
10.0%
Net Price
$255.60
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
CS10.244
Description
AC/DC Power supply unit (PSU) / converter - 20% power reserve - PULS (DIMENSION C-Line series) - 10A (at 24Vdc; ambient less than 60°C) - 24Vdc-28Vdc (adjustable) / 12A / 240W output - with screw-clamp connections - Single-phase (1AC) input (180Vac-264Vac (200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz)) - DIN rail mounting (60mm width) - equivalent to #CS10244
Specifications
Primary brand
PULS
Main function
Power supply unit
Product series / family name
DIMENSION series
Sub-range name
C-Line series
Functions
AC/DC Power supply unit (PSU) / converter
20% power reserve
20% power reserve
Design
20% power reserve
DC-OK rly. contact output
DC-OK rly. contact output
Supply voltage (AC)
180Vac-264Vac (200Vac / 208Vac / 220Vac / 230Vac / 240Vac nom.; 47-63Hz)
155Vac turn-ON voltage
137Vac shutdown voltage (steady-state)
155Vac turn-ON voltage
137Vac shutdown voltage (steady-state)
Display
"DC-OK" LED
Type of network
Single-phase (1AC)
Rated current
12A (at 24Vdc; ambient less than 45°C)
10A (at 24Vdc; ambient less than 60°C)
10.3A (at 28Vdc; ambient less than 45°C)
8.6A (at 28Vdc; ambient less than 60°C)
10A (at 24Vdc; ambient less than 60°C)
10.3A (at 28Vdc; ambient less than 45°C)
8.6A (at 28Vdc; ambient less than 60°C)
Rated power
288W (ambient less than 45°C)
240W (ambient less than 60°C)
240W (ambient less than 60°C)
Output voltage (DC)
24Vdc-28Vdc (adjustable)
100mV turn-ON overshoot
100mV turn-ON overshoot
Hold time
45ms (buffer time at 230Vac input)
Connection type
screw-clamp connections
Protection functions
output overvoltage protection (34Vdc typ. / 39Vdc max.)
NTC (input inrush current limiter)
Overload / short-circuit current -- min. 14A (max. 18A) at load impedance <100mΩ
Series / parallel operation -- Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case 1 power supply unit fails. The simplest way is to put 2 power supplies in parallel. This is called a 1+1 redundancy. In case 1 power supply unit fails the other 1 is automatically able to support the load current without any interruption
Back-feeding loads max. 35V -- The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is ON or OFF. The absorbing energy can be calculated according to the built-in large sized output capacitor.
NTC (input inrush current limiter)
Overload / short-circuit current -- min. 14A (max. 18A) at load impedance <100mΩ
Series / parallel operation -- Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case 1 power supply unit fails. The simplest way is to put 2 power supplies in parallel. This is called a 1+1 redundancy. In case 1 power supply unit fails the other 1 is automatically able to support the load current without any interruption
Back-feeding loads max. 35V -- The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is ON or OFF. The absorbing energy can be calculated according to the built-in large sized output capacitor.
Efficiency
0.913 (230Vac input)
Mounting mode
DIN rail mounting
Time delay
220ms start-up delay (200-240Vac input)
35ms rise time (nominal input; constant full current load; 0mF load capacitance)
75ms rise time (nominal input; constant full current load; 10mF load capacitance)
35ms rise time (nominal input; constant full current load; 0mF load capacitance)
75ms rise time (nominal input; constant full current load; 10mF load capacitance)
Dimensions
W60mm x H124mm x D117mm
Net Width (mm)
60 mm
Material
Aluminium housing
Ambient air temperature for operation
0...+70 °C
Current consumption
2.2A (230Vac input; full 24Vdc output)
59A peak max. inrush (at 230Vac input)
59A peak max. inrush (at 230Vac input)
Power dissipation/losses
(230Vac input; full output load) 22.9 W
Power factor (cos phi)
(230Vac input) 0.52
Manufacturer product status
Commercialized
Equivalent to
CS10244
Capacitance
(output stage) 7000 μF
Compliant with standard(s)
CE marking
UL 508
UL 60950-1
IEC 60950-1 CB-Scheme
Class I Div. 2 HazLoc
GL Marine
ABS Marine
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-4 Emission for industrial environments
EN 55011 / EN 55022 class B Disturbance characteristics
UL 508
UL 60950-1
IEC 60950-1 CB-Scheme
Class I Div. 2 HazLoc
GL Marine
ABS Marine
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-4 Emission for industrial environments
EN 55011 / EN 55022 class B Disturbance characteristics
Electrical durability
(at 40°C; 5A output; 1AC 230Vac input) 118000 hours
(at 25°C; 5A output; 1AC 230Vac input) 334000 hours
(at 40°C; 10A output; 1AC 230Vac input) 75000 hours
(at 25°C; 10A output; 1AC 230Vac input) 212000 hours
(at 40°C; 12A output; 1AC 230Vac input) 64000 hours
(at 25°C; 12A output; 1AC 230Vac input) 181000 hours
(at 25°C; 5A output; 1AC 230Vac input) 334000 hours
(at 40°C; 10A output; 1AC 230Vac input) 75000 hours
(at 25°C; 10A output; 1AC 230Vac input) 212000 hours
(at 40°C; 12A output; 1AC 230Vac input) 64000 hours
(at 25°C; 12A output; 1AC 230Vac input) 181000 hours
Benefits
AC 200-240V Single-Phase Input
Width only 60mm
Efficiency up to 91.3%
Easy fuse breaking due to high overload peak current
20% Output power reserve
Full Output Power up to +60°C
3 Year warranty
The DIMENSION C-Line units are cost optimized power supplies without compromising quality reliability and performance. The C-Line is part of the DIMENSION power supply family existing alongside the high featured Q-Line. The CS10.244 includes all the essential basic functions and the devices have a power reserve of 20%. This extra current may even be used continuously at temperatures up to +45°C. The most important features are the small size high efficiency and the wide temperature range. The unit has an input for 200-240V mains only. This supports regional applications and offers additional cost savings without sacrificing functionality. High immunity to transients and power surges as well as low electromagnetic emission and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
Width only 60mm
Efficiency up to 91.3%
Easy fuse breaking due to high overload peak current
20% Output power reserve
Full Output Power up to +60°C
3 Year warranty
The DIMENSION C-Line units are cost optimized power supplies without compromising quality reliability and performance. The C-Line is part of the DIMENSION power supply family existing alongside the high featured Q-Line. The CS10.244 includes all the essential basic functions and the devices have a power reserve of 20%. This extra current may even be used continuously at temperatures up to +45°C. The most important features are the small size high efficiency and the wide temperature range. The unit has an input for 200-240V mains only. This supports regional applications and offers additional cost savings without sacrificing functionality. High immunity to transients and power surges as well as low electromagnetic emission and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
Ripple
50mVpp (20Hz...20MHz; 50Ω)
MTBF (Mean Time Between Failures)
910000h (at 40°C; 230Vac input; MTBF SN 29500 IEC 61709)
774000h (at 40°C; 230Vac input; MTBF SN 29500 IEC 61709)
1574000h (at 25°C; 230Vac input; MTBF SN 29500 IEC 61709)
530000h (at 40°C; 230Vac input; MTBF MIL HDBK 217F)
477000h (at 40°C; 230Vac input; MTBF MIL HDBK 217F)
726000h (at 25°C; 230Vac input; MTBF MIL HDBK 217F)
774000h (at 40°C; 230Vac input; MTBF SN 29500 IEC 61709)
1574000h (at 25°C; 230Vac input; MTBF SN 29500 IEC 61709)
530000h (at 40°C; 230Vac input; MTBF MIL HDBK 217F)
477000h (at 40°C; 230Vac input; MTBF MIL HDBK 217F)
726000h (at 25°C; 230Vac input; MTBF MIL HDBK 217F)
Related Documents
Name | Last Update | Language |
---|---|---|
PULS - Power supply units - Catalog.pdf | 01 Oct 2021 | English (US) |
PULS - CS10-244 - Datasheet.pdf | 01 Oct 2021 | English (US) |