Eaton
EGF0214B3200000000
Enclosed passive-filtered Adjustable Variable Speed / Frequency Drive (AFD/VSD/VFD) / Inverter - Eaton / Cutler-Hammer (EGF) - Rated input voltage (3-phase (3P)) 480Vac - Rated output current 21A (Low overload IL) - Rated power 11kW (Low overload IL) / 15HP (Low overload IL) - Frame size 2 - UL type 3R / NEMA 3R - with Ethernet/IP / Modbus TCP / Modbus RTU / BACnet MS/TP communication capability - Surface / Wall mounting - with conformal coated PCB - with Brake chopper
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Brand
SKU
EGF0214B3200000000
Please add this item to cart to request a quote.
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Eaton - EGFEGF0214B3200000000
Description
Enclosed passive-filtered Adjustable Variable Speed / Frequency Drive (AFD/VSD/VFD) / Inverter - Eaton / Cutler-Hammer (EGF) - Rated input voltage (3-phase (3P)) 480Vac - Rated output current 21A (Low overload IL) - Rated power 11kW (Low overload IL) / 15HP (Low overload IL) - Frame size 2 - UL type 3R / NEMA 3R - with Ethernet/IP / Modbus TCP / Modbus RTU / BACnet MS/TP communication capability - Surface / Wall mounting - with conformal coated PCB - with Brake chopper
Specifications
Primary brand
Eaton
Secondary brand
Cutler-Hammer
Main function
Variable Speed / Frequency Drive (VSD/VFD) / Inverter
Product series / family name
EGF
Network frequency
(input) 45-66 Hz
(output) 0-400 Hz
(output) 0-400 Hz
Functions
Enclosed passive-filtered Adjustable Variable Speed / Frequency Drive (AFD/VSD/VFD) / Inverter
Brake chopper
Circuit breaker power disconnect
Brake chopper
Circuit breaker power disconnect
Supply voltage (AC)
480Vac
Type of network
3-phase input (3P)
Rated current
21A (Low overload IL)
Rated active power (kW)
11kW (Low overload IL)
Rated power (HP)
15HP (Low overload IL)
Protection functions
Overvoltage
Overvoltage trip limit
Undervoltage
Undervoltage trip limit
Earth fault
Input phase supervision
Motor phase supervision
Overcurrent
Unit overtemperature
Motor overload
Motor stall
Motor underload
DC bus overvoltage control
Short-circuit
Surge protection
Overvoltage trip limit
Undervoltage
Undervoltage trip limit
Earth fault
Input phase supervision
Motor phase supervision
Overcurrent
Unit overtemperature
Motor overload
Motor stall
Motor underload
DC bus overvoltage control
Short-circuit
Surge protection
Communication protocol
Ethernet/IP
Modbus TCP
Modbus RTU
BACnet MS/TP
Modbus TCP
Modbus RTU
BACnet MS/TP
Mounting mode
Surface
Wall
Wall
Operating mode
Frequency control
Speed control
Open-loop speed control
Open-loop torque control
Speed control
Open-loop speed control
Open-loop torque control
Digital inputs
1 x digital input (FWD)
1 x digital input (REV)
1 x digital input (External Fault)
1 x digital input (Fault Reset)
1 x digital input (Preset Speed B0)
1 x digital input (Preset Speed B1)
1 x digital input (Emergency Stop TI-)
1 x digital input (Force Remote TI+)
1 x digital input (REV)
1 x digital input (External Fault)
1 x digital input (Fault Reset)
1 x digital input (Preset Speed B0)
1 x digital input (Preset Speed B1)
1 x digital input (Emergency Stop TI-)
1 x digital input (Force Remote TI+)
Digital outputs
1 x digital output (READY)
2 x digital outputs (SPDT Single Pole Double Throw contact type)
1 x digital output (NO contact type)
2 x digital outputs (SPDT Single Pole Double Throw contact type)
1 x digital output (NO contact type)
Analog inputs
2 x analog inputs (4-20mA / 0-10V DC)
Analog outputs
1 x analog output (Output Frequency; 4-20mA)
1 x analog output (Motor Current; 4-20mA)
1 x analog output (Motor Current; 4-20mA)
Degree of protection
UL type 3R
NEMA 3R
NEMA 3R
Ambient air temperature for operation
-10...+40 °C
Ambient air temperature for storage
-40...+70 °C
Chemical resistance
conformal coated PCB
Application type
Filtered drive
Manufacturer product status
Commercialized
Compliant with standard(s)
UL 508C
IEC 60721-3-3
EN 61800-3
EN 61800-5-1
IEC 60721-3-3
EN 61800-3
EN 61800-5-1
Benefits
Tuned passive filter
Delivers 5–8% THD
Generator compatible
Uses the same DG1; SVX or SPX drive that is stocked in the warehouse
Simple to retrofit
Provides a low-impedance path to ground for the harmonic frequencies
Meets IEEE 519-2014
Excellent cost for performance
Small footprint; compact enclosure design
Insensitive to voltage imbalance
Customizable cover control options
Padlockable disconnect
Delivers 5–8% THD
Generator compatible
Uses the same DG1; SVX or SPX drive that is stocked in the warehouse
Simple to retrofit
Provides a low-impedance path to ground for the harmonic frequencies
Meets IEEE 519-2014
Excellent cost for performance
Small footprint; compact enclosure design
Insensitive to voltage imbalance
Customizable cover control options
Padlockable disconnect
Degree of pollution
2
Related Documents
Name | Last Update | Language |
---|---|---|
Eaton - PowerXL M-Max SVX H-Max SPX EGF CFX HCX CPX RGX LCX SPA SPN SPI - Catalogue.pdf | 23 Jun 2020 | English (US) |