Eaton
SVXF071D1200010000
Enclosed Adjustable Variable Speed / Frequency Drive (AFD/VSD/VFD) / Inverter - Eaton / Cutler-Hammer (SVX) - Rated input voltage (3-phase (3P)) 208Vac - Rated output current 3.5A (High overload IH) - Rated power 0.55kW (High overload IH) / 3/4HP (High overload IH) - Frame size FR4 - UL type 1 / NEMA 1 - with EMI filter - with RS-232 communication capability - with Brake chopper + Non-bypass light kit
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Brand
SKU
SVXF071D1200010000
Please add this item to cart to request a quote.
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Eaton - SVXSVXF071D1200010000
Description
Enclosed Adjustable Variable Speed / Frequency Drive (AFD/VSD/VFD) / Inverter - Eaton / Cutler-Hammer (SVX) - Rated input voltage (3-phase (3P)) 208Vac - Rated output current 3.5A (High overload IH) - Rated power 0.55kW (High overload IH) / 3/4HP (High overload IH) - Frame size FR4 - UL type 1 / NEMA 1 - with EMI filter - with RS-232 communication capability - with Brake chopper + Non-bypass light kit
Specifications
Primary brand
Eaton
Secondary brand
Cutler-Hammer
Main function
Variable Speed / Frequency Drive (VSD/VFD) / Inverter
Product series / family name
SVX
Network frequency
(input) 45-66 Hz
(output) 0-320 Hz
(output) 0-320 Hz
Functions
Enclosed Adjustable Variable Speed / Frequency Drive (AFD/VSD/VFD) / Inverter
Brake chopper
Non-bypass light kit
Circuit breaker power disconnect
Electronic reversing
DC braking
PID setpoint controller
Critical speed lockout
Current (torque) limit
Adjustable acceleration/deceleration
Linear or S curve accel/decel
Jog at preset speed
Thread/preset speeds
Automatic restart
Coasting motor start
Coast or ramp stop selection
Carrier frequency adjustment
Non-bypass light (white = Power ON; green = RUN; red = FAULT)
Brake chopper
Non-bypass light kit
Circuit breaker power disconnect
Electronic reversing
DC braking
PID setpoint controller
Critical speed lockout
Current (torque) limit
Adjustable acceleration/deceleration
Linear or S curve accel/decel
Jog at preset speed
Thread/preset speeds
Automatic restart
Coasting motor start
Coast or ramp stop selection
Carrier frequency adjustment
Non-bypass light (white = Power ON; green = RUN; red = FAULT)
Supply voltage (AC)
208Vac
Type of network
3-phase input (3P)
Rated current
3.5A (High overload IH)
Rated active power (kW)
0.55kW (High overload IH)
Rated power (HP)
3/4HP (High overload IH)
Protection functions
Phase Rotation Insensitive
Input Phase Loss
Input Overvoltage
Output Short-Circuit
Output Ground Fault
Output Phase Protection
Overtemperature
DC Overvoltage
Drive Overload
Motor Overload
Local/remote keypad
Keypad Lockout
Fault Alarm Output
Built-in Diagnostics
Input Phase Loss
Input Overvoltage
Output Short-Circuit
Output Ground Fault
Output Phase Protection
Overtemperature
DC Overvoltage
Drive Overload
Motor Overload
Local/remote keypad
Keypad Lockout
Fault Alarm Output
Built-in Diagnostics
Communication protocol
RS-232
Operating mode
Frequency control (V/f)
Sensorless vector control
IR and slip compensation
Sensorless vector control
IR and slip compensation
Digital inputs
6 x digital inputs (programmable)
Digital outputs
2 x digital outputs (SPDT Single Pole Double Throw contact type)
1 x digital output (Open collector)
1 x digital output (Open collector)
Analog inputs
2 x analog inputs (0-20mA / 4-20mA / 0-10V DC)
Analog outputs
1 x analog output (0-20mA / 4-20mA / 0-10V DC / 2-10V DC)
Degree of protection
UL type 1
NEMA 1
NEMA 1
Ambient air temperature for operation
0...+40 °C
Ambient air temperature for storage
-40...+60 °C
Technology used in component
EMI filter
Application type
General-purpose drive
Manufacturer product status
Commercialized
Compliant with standard(s)
UL 508C
Benefits
Dual rated for both constant torque (CT) / high overload (IH) and variable torque (VT) / low overload applications
Optional Brake Chopper for external braking applications
High-performance drive option uses an Eaton SPX (IH) drive that allows for increased functionality and performance
Available circuit breaker; motor circuit protector; isolation fusing and surge protection device options to provide input power protection
Optional 3% input and output reactors provide a reduction in voltage and current harmonics on both line and load side
Bypass options include a standard three-contactor design and a reduced voltage soft starter design
Output contactor option provides a means for positive disconnection of the drive output from the motor terminals
MotoRX and dV/dt filter options are used to reduce transients voltages at the motor terminals
Customizable cover control options
Padlockable disconnection
Optional Brake Chopper for external braking applications
High-performance drive option uses an Eaton SPX (IH) drive that allows for increased functionality and performance
Available circuit breaker; motor circuit protector; isolation fusing and surge protection device options to provide input power protection
Optional 3% input and output reactors provide a reduction in voltage and current harmonics on both line and load side
Bypass options include a standard three-contactor design and a reduced voltage soft starter design
Output contactor option provides a means for positive disconnection of the drive output from the motor terminals
MotoRX and dV/dt filter options are used to reduce transients voltages at the motor terminals
Customizable cover control options
Padlockable disconnection
Related Documents
Name | Last Update | Language |
---|---|---|
Eaton - PowerXL M-Max SVX H-Max SPX EGF CFX HCX CPX RGX LCX SPA SPN SPI - Catalogue.pdf | 23 Jun 2020 | English (US) |