ABB
T7LQ1200C0KA3AULT7L 1200 PR232/P LSI In=1200A 3p F F UL/CSA 100% (T7LQ1200C0KA3AUL)
T7L 1200 PR232/P LSI In=1200A 3p F F UL/CSA 100% (T7LQ1200C0KA3AUL)
Moulded / Molded Case Circuit Breaker (MCCB) with standard lever operating mechanism - UL 100% rated version - ABB / SACE (Tmax T (UL/CSA) series) - T7L 1200 PR232/P LSI In=1200A 3p F F UL/CSA 100% - 3-poles (3P3d) - Rated current 1200A - Short circuit breaking capacity (Icu) 100kA (480Vac) - Electronic (PR232/P LSI) trip unit - equivalent to T7LQ1200C0KA3AUL
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Brand
SKU
T7LQ1200C0KA3AUL
Online Price
$18,688.37
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
T7LQ1200C0KA3AULABB - Tmax T7
Description
Moulded / Molded Case Circuit Breaker (MCCB) with standard lever operating mechanism - UL 100% rated version - ABB / SACE (Tmax T (UL/CSA) series) - T7L 1200 PR232/P LSI In=1200A 3p F F UL/CSA 100% - 3-poles (3P3d) - Rated current 1200A - Short circuit breaking capacity (Icu) 100kA (480Vac) - Electronic (PR232/P LSI) trip unit - equivalent to T7LQ1200C0KA3AUL
Specifications
Primary brand
ABB
Secondary brand
SACE
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Tmax T (UL/CSA)
Sub-range name
T7L complete breakers
Functions
Moulded / Molded Case Circuit Breaker (MCCB)
Design
standard lever operating mechanism
UL 100% rated version
UL 100% rated version
Poles
3-poles (3P3d)
Rated current
1200A
Trip current rating
1200 AT
Frame current rating
1200 AF
Rated voltage (AC)
600Vac
Connection type
Ring-lug or bar connections
Ultimate short circuit current breaking capacity (Icu)
150kA (240Vac)
100kA (480Vac)
65kA (600Vac)
100kA (480Vac)
65kA (600Vac)
Trip unit type
Technology = Electronic
Series = PR232/P LSI
Protection = LSI
Display = none
Series = PR232/P LSI
Protection = LSI
Display = none
Protection functions
(L) Protection against overload
(S) Protection against short-circuit with time delay
(I) Instantaneous protection against short-circuit
(S) Protection against short-circuit with time delay
(I) Instantaneous protection against short-circuit
Protection settings
L - Protection against overload -- adjustable 0.4...1 x In (480A...1200A)
S - Protection against short-circuit with time delay -- adjustable 0.6...10 x In (720A...12000A); with adjustable time trip curve
I - Instantaneous protection against short-circuit -- adjustable 1...12 x In (1200A...14400A)
S - Protection against short-circuit with time delay -- adjustable 0.6...10 x In (720A...12000A); with adjustable time trip curve
I - Instantaneous protection against short-circuit -- adjustable 1...12 x In (1200A...14400A)
Operating mode
Toggle
Order code / Manufacturer SKU
T7L 1200 PR232/P LSI In=1200A 3p F F UL/CSA 100%
Manufacturer product status
Commercialized
Equivalent to
T7LQ1200C0KA3AUL
Compliant with standard(s)
UL 489
CSA C22.2
CSA C22.2
Related Documents
Name | Last Update | Language |
---|---|---|
ABB - 2013 Product selector - 17 Moulded Case Circuit breakers - Catalogue.pdf | 02 Feb 2023 | English (US) |