ABB
T8VQD3GC0ABA0ABBT8V 2000 PR331/P LSI In=2000A 3p F F UL/CSA 100% (T8VQD3GC0ABA0ABB)
T8V 2000 PR331/P LSI In=2000A 3p F F UL/CSA 100% (T8VQD3GC0ABA0ABB)
Moulded / Molded Case Circuit Breaker (MCCB) with closing solen. (24Vdc) + spring charging mtr. (24-30Vac/dc) + undervoltage solen. (24Vdc) + bell alarm + btn. guard - UL 100% rated version - ABB / SACE (Tmax T (UL/CSA) series) - T8V 2000 PR331/P LSI In=2000A 3p F F UL/CSA 100% - 3-poles (3P3d) - Rated current 2000A - Short circuit rating 125kA (480Vac; UL489) - Electronic (PR331/P LSI) trip unit - 4 aux. contacts digital (24V) - equivalent to T8VQD3GC0ABA0ABB / T8V2000PR331PLSIIn2000A3pFFULCSA100
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Brand
SKU
T8VQD3GC0ABA0ABB
Online Price
$19,287.00
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
T8VQD3GC0ABA0ABBABB - Tmax T UL/CSA
Description
Moulded / Molded Case Circuit Breaker (MCCB) with closing solen. (24Vdc) + spring charging mtr. (24-30Vac/dc) + undervoltage solen. (24Vdc) + bell alarm + btn. guard - UL 100% rated version - ABB / SACE (Tmax T (UL/CSA) series) - T8V 2000 PR331/P LSI In=2000A 3p F F UL/CSA 100% - 3-poles (3P3d) - Rated current 2000A - Short circuit rating 125kA (480Vac; UL489) - Electronic (PR331/P LSI) trip unit - 4 aux. contacts digital (24V) - equivalent to T8VQD3GC0ABA0ABB / T8V2000PR331PLSIIn2000A3pFFULCSA100
Specifications
Primary brand
ABB
Secondary brand
SACE
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Tmax T (UL/CSA)
Sub-range name
T8V complete breakers
Functions
Moulded / Molded Case Circuit Breaker (MCCB)
Design
closing solen. (24Vdc)
spring charging mtr. (24-30Vac/dc)
undervoltage solen. (24Vdc)
bell alarm
btn. guard
UL 100% rated version
spring charging mtr. (24-30Vac/dc)
undervoltage solen. (24Vdc)
bell alarm
btn. guard
UL 100% rated version
Poles
3-poles (3P3d)
Rated current
2000A
Trip current rating
2000 AT
Frame current rating
2000 AF
Rated voltage (AC)
600Vac
Connection type
Ring-lug or bar connections
Short circuit breaking rating
125kA (240Vac; UL489)
125kA (480Vac; UL489)
100kA (600Vac; UL489)
125kA (480Vac; UL489)
100kA (600Vac; UL489)
Trip unit type
Technology = Electronic
Series = PR331/P LSI
Protection = LSI
Display = none
Series = PR331/P LSI
Protection = LSI
Display = none
Protection functions
(L) Protection against overload
(S) Protection against short-circuit with time delay
(I) Instantaneous protection against short-circuit
(S) Protection against short-circuit with time delay
(I) Instantaneous protection against short-circuit
Protection settings
L - Protection against overload -- adjustable 0.4...1 x In (800A...2000A)
S - Protection against short-circuit with time delay -- adjustable 0.6...10 x In (1200A...20000A); with adjustable time trip curve
I - Instantaneous protection against short-circuit -- adjustable 1.5...15 x In (3000A...30000A)
S - Protection against short-circuit with time delay -- adjustable 0.6...10 x In (1200A...20000A); with adjustable time trip curve
I - Instantaneous protection against short-circuit -- adjustable 1.5...15 x In (3000A...30000A)
Operating mode
Stored energy closing/opening mechanism
Contacts type
4 aux. contacts digital (24V)
Mechanical durability (at no load)
15000 operations
Order code / Manufacturer SKU
T8V 2000 PR331/P LSI In=2000A 3p F F UL/CSA 100%
Manufacturer product status
Commercialized
Equivalent to
T8VQD3GC0ABA0ABB
T8V2000PR331PLSIIn2000A3pFFULCSA100
T8V2000PR331PLSIIn2000A3pFFULCSA100
Compliant with standard(s)
UL 489
CSA C22.2
CSA C22.2
Related Documents
Name | Last Update | Language |
---|---|---|
ABB - 2013 Product selector - 17 Moulded Case Circuit breakers - Catalogue.pdf | 02 Feb 2023 | English (US) |