ABB
1SAM451200R1016MS165-54B
MS165-54B
Thermal-Magnetic Motor Protection Circuit Breaker (MPCB) / Manual motor starter protector with shocks and vibration withstand - fire and smoke safety - IEC 60077 / IEC 61373 / EN 45545-2 compliant - ABB (MS165 series) - MS165-54B - rated current 40A...54A (adjustable) - 22kW (400/415Vac) / 40HP (UL/CSA; 440-480Vac) - ON/OFF/TRIP rotary knob operation - Short circuit breaking capacity (Icu) 50kA (400Vac) - Screw-clamp connections - IP20
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Brand
SKU
1SAM451200R1016
Online Price
$895.94
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
1SAM451200R1016ABB - MS165 series Motor Protection Circuit Breakers (MPCBs)
Description
Thermal-Magnetic Motor Protection Circuit Breaker (MPCB) / Manual motor starter protector with shocks and vibration withstand - fire and smoke safety - IEC 60077 / IEC 61373 / EN 45545-2 compliant - ABB (MS165 series) - MS165-54B - rated current 40A...54A (adjustable) - 22kW (400/415Vac) / 40HP (UL/CSA; 440-480Vac) - ON/OFF/TRIP rotary knob operation - Short circuit breaking capacity (Icu) 50kA (400Vac) - Screw-clamp connections - IP20
Specifications
Primary brand
ABB
Main function
Motor Protection Circuit Breaker (MPCB)
Product series / family name
MS165 series
Functions
Thermal-Magnetic Motor Protection Circuit Breaker (MPCB) / Manual motor starter protector
magnetic trip indication (makes fault troubleshooting easier by differentiating thermal fault from short circuit fault)
magnetic trip indication (makes fault troubleshooting easier by differentiating thermal fault from short circuit fault)
Design
shocks and vibration withstand
fire and smoke safety
IEC 60077 / IEC 61373 / EN 45545-2 compliant
fire and smoke safety
IEC 60077 / IEC 61373 / EN 45545-2 compliant
Poles
3-poles (3P)
Rated current
40A...54A (adjustable)
48.3A (UL/CSA FLA Full Load Amps; 200Vac)
267A (UL/CSA LRA Locked Rotor Amperes; 200Vac)
46.2A (UL/CSA FLA Full Load Amps; 208Vac)
257A (UL/CSA LRA Locked Rotor Amperes; 208Vac)
54A (UL/CSA FLA Full Load Amps; 220-240Vac)
290A (UL/CSA LRA Locked Rotor Amperes; 220-240Vac)
52A (UL/CSA FLA Full Load Amps; 440-480Vac)
290A (UL/CSA LRA Locked Rotor Amperes; 440-480Vac)
52A (UL/CSA FLA Full Load Amps; 550-600Vac)
290A (UL/CSA LRA Locked Rotor Amperes; 550-600Vac)
48.3A (UL/CSA FLA Full Load Amps; 200Vac)
267A (UL/CSA LRA Locked Rotor Amperes; 200Vac)
46.2A (UL/CSA FLA Full Load Amps; 208Vac)
257A (UL/CSA LRA Locked Rotor Amperes; 208Vac)
54A (UL/CSA FLA Full Load Amps; 220-240Vac)
290A (UL/CSA LRA Locked Rotor Amperes; 220-240Vac)
52A (UL/CSA FLA Full Load Amps; 440-480Vac)
290A (UL/CSA LRA Locked Rotor Amperes; 440-480Vac)
52A (UL/CSA FLA Full Load Amps; 550-600Vac)
290A (UL/CSA LRA Locked Rotor Amperes; 550-600Vac)
Rated active power (kW)
22kW (400/415Vac)
Rated power (HP)
15HP (UL/CSA; 200Vac)
15HP (UL/CSA; 208Vac)
20HP (UL/CSA; 220-240Vac)
40HP (UL/CSA; 440-480Vac)
50HP (UL/CSA; 550-600Vac)
15HP (UL/CSA; 208Vac)
20HP (UL/CSA; 220-240Vac)
40HP (UL/CSA; 440-480Vac)
50HP (UL/CSA; 550-600Vac)
Rated operating voltage (Ue)
690 V
Rated Voltage (DC)
250
Rated impulse voltage (Uimp)
6 kV
Rated insulation voltage (Ui)
1000 V
Connection type
Screw-clamp connections
Ultimate short circuit current breaking capacity (Icu)
50kA (230Vac)
50kA (400Vac)
45kA (415Vac)
45kA (440Vac)
20kA (500Vac)
8kA (690Vac)
100kA (250Vdc)
50kA (400Vac)
45kA (415Vac)
45kA (440Vac)
20kA (500Vac)
8kA (690Vac)
100kA (250Vdc)
Service short circuit current breaking capacity (Ics)
30kA (230Vac)
30kA (400Vac)
30kA (415Vac)
30kA (440Vac)
20kA (500Vac)
6kA (690Vac)
100kA (250Vdc)
30kA (400Vac)
30kA (415Vac)
30kA (440Vac)
20kA (500Vac)
6kA (690Vac)
100kA (250Vdc)
Trip unit type
Thermal-Magnetic (adjustable)
Protection functions
Short circuit protection
Phase failure / phase loss
Thermal overload Class 10
Phase failure / phase loss
Thermal overload Class 10
Protection settings
Magnetic protection (Short-circuit) -- short-circuit pickup current fixed at 810A
Thermal protection (Overload) -- 40A...54A (adjustable)
Thermal protection (Overload) -- 40A...54A (adjustable)
Mounting mode
Mounts on DIN rail or mounting plate
Operating mode
ON/OFF/TRIP rotary knob
Degree of protection
IP20
Net Height (mm)
142.65 mm
Net Width (mm)
55 mm
Net Depth (mm)
122 mm
Ambient air temperature for operation
-25...+60 °C
Ambient air temperature for storage
-50...+80 °C
Electrical durability (with load)
25 000 operations
Mechanical durability (at no load)
50 000 operations
Minimum current
40 A
Maximum current
54 A
Application type
Thermal-magnetic
Order code / Manufacturer SKU
MS165-54B
Manufacturer product status
Commercialized
EAN code
4013614522215
Compliant with standard(s)
IEC 60947-2
IEC 60947-4-1
IEC 60947-1
IEC60077-1 (applicable parts)
IEC60077-2 (applicable parts)
IEC61373 (category 1; class B)
EN 45545-2
IEC 60947-4-1
IEC 60947-1
IEC60077-1 (applicable parts)
IEC60077-2 (applicable parts)
IEC61373 (category 1; class B)
EN 45545-2
Degree of pollution
3
Related Documents
Name | Last Update | Language |
---|---|---|
ABB - Motor protection and control - Catalogue 2020.pdf | 22 Aug 2022 | English (US) |