Schneider Electric
56192
Earth-leakage relay (DIN rail) - Schneider Electric (Vigirex RH99M) - Residual current sensitivity (30mA-30A; with time delay 0-4.5s) 0.03-30A - Supply voltage (AC 50/60Hz 55-110%) 110-130V
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Brand
SKU
56192
Online Price
$2,700.00
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Description
Earth-leakage relay (DIN rail) - Schneider Electric (Vigirex RH99M) - Residual current sensitivity (30mA-30A; with time delay 0-4.5s) 0.03-30A - Supply voltage (AC 50/60Hz 55-110%) 110-130V
Specifications
Primary brand
Schneider Electric
Secondary brand
Merlin Gerin
Product series / family name
Vigirex
Sub-range name
RH99M
Size in modules (1 module = 18mm)
3 Module(s)
Protection settings
Instantaneous 0.03-30A
Adjustable 9 settings 0.1-30A
Adjustable 9 settings 0.1-30A
Supply voltage
(AC 50/60Hz 55-110%) 110-130 V
Minimum current
(12V minimum load) 0.01 A
Residual current sensitivity
(30mA-30A; with time delay 0-4.5s) 0.03-30 A
Power consumption
4 VA
Earthing system
TN-S
TT
TT
Manufacturer product status
Commercialized
Compliant with standard(s)
IEC 60695-2-1
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
CISPR 11
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
CISPR 11
Mounting mode
DIN rail
Protection functions
Earth-leakage
Time delay
Adjustable 9 settings 0-4.5 s