Schneider Electric
BMXDRA1605HDiscrete output module X80 - 16O relay - 24Vac or 24-240Vac - severe
Discrete output module X80 - 16O relay - 24Vac or 24-240Vac - severe
Ruggedized AC/DC digital output module - for severe environments (with conformal coating) - Schneider Electric / Modicon (Modicon X80 series) - 16I/Os [16DO (16 x digital outputs (2A; NO rly. contact outputs))] - Supply voltage 19-264Vac (24-240Vac nom.) / 19-30Vdc (24Vdc nom.) - backplane / rack mounting - with 1 x 20-pin removable term. blck. (caged; screw or spring removable term.; sold separately) - IP20 - Rated for -13...+158°F / -25...+70°C ambient - IEC/EN61131-2 conformity
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Brand
SKU
BMXDRA1605H
Online Price
$521.00
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Schneider Electric - Modicon X80 I/O modulesBMXDRA1605H
Description
Ruggedized AC/DC digital output module - for severe environments (with conformal coating) - Schneider Electric / Modicon (Modicon X80 series) - 16I/Os [16DO (16 x digital outputs (2A; NO rly. contact outputs))] - Supply voltage 19-264Vac (24-240Vac nom.) / 19-30Vdc (24Vdc nom.) - backplane / rack mounting - with 1 x 20-pin removable term. blck. (caged; screw or spring removable term.; sold separately) - IP20 - Rated for -13...+158°F / -25...+70°C ambient - IEC/EN61131-2 conformity
Specifications
Primary brand
Schneider Electric
Secondary brand
Modicon
Main function
I/O unit
Product series / family name
Modicon X80
Sub-range name
Modicon X80 I/O modules
Functions
Ruggedized AC/DC digital output module
Design
for severe environments (with conformal coating)
IEC/EN61131-2 conformity
IEC/EN61131-2 conformity
Supply voltage (AC)
19-264Vac (24-240Vac nom.)
Supply voltage (DC)
19-30Vdc (24Vdc nom.)
Display
1 LED (Green) RUN
1 LED per channel (Green) channel diagnostic
1 LED (Red) ERR
1 LED (Red) I/O
1 LED per channel (Green) channel diagnostic
1 LED (Red) ERR
1 LED (Red) I/O
Connection type
1 x 20-pin removable term. blck. (caged; screw or spring removable term.; sold separately)
Mounting mode
backplane / rack mounting
Digital outputs
16 x digital outputs (2A; NO rly. contact outputs)
Degree of protection
IP20
Ambient air temperature for operation
-13...+158°F / -25...+70 °C
Ambient air temperature for storage
-40...+185°F / -40...+85 °C
Humidity
5-95% (at 131°F (55°C) without condensation)
Chemical resistance
IEC/EN 60721-3-3 -- class 3C1; 3C2; 3C3; 3C4 (Concentrations H2S 9900PPB (parts per billion) /SO2 4800PPB / Cl2 200PPB)
IEC/EN 60068-2-52 -- salt mist Kb test severity level 2 (3 x 24-hour cycles; 5% NaCl 40°C/104°F; relative humidity 93%)
ISA S71.04 -- classes G1 to Gx concentrations (H2S 60PPB / SO2 350PPB / Cl2 1450PPB / NO2 12PPB)
Resistant to harsh environment (conformal coated PCB)
IEC/EN 60068-2-52 -- salt mist Kb test severity level 2 (3 x 24-hour cycles; 5% NaCl 40°C/104°F; relative humidity 93%)
ISA S71.04 -- classes G1 to Gx concentrations (H2S 60PPB / SO2 350PPB / Cl2 1450PPB / NO2 12PPB)
Resistant to harsh environment (conformal coated PCB)
Current consumption
79mA (at 3.3Vdc)
Technical compatibility with
Modicon M340 PLCs
Modicon M580 PLCs
Modicon M580 PLCs
Power dissipation/losses
3 W
Order code / Manufacturer SKU
BMXDRA1605H
Manufacturer product status
Commercialized
Compliant with standard(s)
RoHS directive 2011/65/EU
WEEE directive 2012/19/EU
CE
EAC
Merchant Navy
REACH regulations (EC No. 1907/2006)
For USA and Canada -- Hazardous location class I; division 2; groups A;B;C; and D
For European Union -- ATEX for atmosphere Zone 2 (gas) and Zone 22 (dust)
For United Kingdom -- UKEX for atmosphere Zone 2 (gas) and Zone 22 (dust)
For other countries -- IECEx for atmosphere Zone 2 (gas) and/or Zone 22 (dust)
Meets or exceeds IEC60068-2 requirements -- Shocks 30g (vs IEC requirement 15g) / vibrations 3g (vs IEC requirement 1g)
WEEE directive 2012/19/EU
CE
EAC
Merchant Navy
REACH regulations (EC No. 1907/2006)
For USA and Canada -- Hazardous location class I; division 2; groups A;B;C; and D
For European Union -- ATEX for atmosphere Zone 2 (gas) and Zone 22 (dust)
For United Kingdom -- UKEX for atmosphere Zone 2 (gas) and Zone 22 (dust)
For other countries -- IECEx for atmosphere Zone 2 (gas) and/or Zone 22 (dust)
Meets or exceeds IEC60068-2 requirements -- Shocks 30g (vs IEC requirement 15g) / vibrations 3g (vs IEC requirement 1g)
Benefits
Discrete I/O modules in the Modicon X80 offer are standard modules occupying a single slot on the rack. These modules are equipped with one of the following
- A connector for a 20-way caged / screw clamp or spring-type removable terminal block
- A connector for a 40-way caged or spring-type removable terminal block
- One or two 40-way connectors
This wide range of discrete I/O can be used to meet whatever requirements arise in terms of
- Functions -- AC or DC I/O (positive or negative logic)
- Modularity -- 8 / 16 / 32 or 64 channels per module
The inputs receive signals from the sensors and perform the following functions
- Acquisition
- Adaptation
- Electrical isolation
- Filtering
- Protection against interference signals
- A connector for a 20-way caged / screw clamp or spring-type removable terminal block
- A connector for a 40-way caged or spring-type removable terminal block
- One or two 40-way connectors
This wide range of discrete I/O can be used to meet whatever requirements arise in terms of
- Functions -- AC or DC I/O (positive or negative logic)
- Modularity -- 8 / 16 / 32 or 64 channels per module
The inputs receive signals from the sensors and perform the following functions
- Acquisition
- Adaptation
- Electrical isolation
- Filtering
- Protection against interference signals
Location of origin
France (FR)
Related Documents
Name | Last Update | Language |
---|---|---|
Download official PDF datasheet for BMXDRA1605H from Schneider Electric | 18 Jun 2021 | English (US) |
Schneider Electric - Modules platform - Modicon X80 - Catalog.pdf | 08 Jan 2023 | English (US) |