Schneider Electric
HJA36030M71Motor circuit protector PowerPact H-Frame 3P 30A 600Vac/250Vdc 25kA I-Line MCP (I) 80% rated
Motor circuit protector PowerPact H-Frame 3P 30A 600Vac/250Vdc 25kA I-Line MCP (I) 80% rated
Electronic Motor Protector Circuit Breaker (MPCB) / Manual Motor Starter / Motor Circuit Protector (MCP) - PowerPact H-Frame 150 MCP (I) 3P 30A 600Vac/250Vdc 25kA I-line ABC - 80% rated - Square D by Schneider Electric - 3-poles (3P) - Rated current 30A - Short circuit breaking capacity 25kA (600Y/347Vac; UL489) - Thermal-Magnetic (adjustable) (MCP (I)) trip unit - I-line connection (ABC phases)
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Brand
SKU
HJA36030M71
Online Price
$1,668.00
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
HJA36030M71Schneider Electric - PowerPact H-Frame - PowerPact HJA
Description
Electronic Motor Protector Circuit Breaker (MPCB) / Manual Motor Starter / Motor Circuit Protector (MCP) - PowerPact H-Frame 150 MCP (I) 3P 30A 600Vac/250Vdc 25kA I-line ABC - 80% rated - Square D by Schneider Electric - 3-poles (3P) - Rated current 30A - Short circuit breaking capacity 25kA (600Y/347Vac; UL489) - Thermal-Magnetic (adjustable) (MCP (I)) trip unit - I-line connection (ABC phases)
Specifications
Primary brand
Square D by Schneider Electric
Main function
Motor Protection Circuit Breaker (MPCB)
Product series / family name
PowerPacT H-Frame motor protectors
Sub-range name
PowerPacT HJA
Functions
Electronic Motor Protector Circuit Breaker (MPCB) / Manual Motor Starter / Motor Circuit Protector (MCP)
Design
PowerPact H-Frame 150 MCP (I) 3P 30A 600Vac/250Vdc 25kA I-line ABC
80% rated
80% rated
Poles
3-poles (3P)
Rated current
30A
Trip current rating
30 AT
Frame current rating
150 AF
Rated operating voltage (Ue)
690 V
Rated Voltage (DC)
250Vdc
Rated voltage (AC)
600Y/347Vac
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
750 V
Connection type
I-line connection (ABC phases)
Short circuit breaking rating
100kA (240Vac; UL489)
65kA (480Vac; UL489)
65kA (480Y/277Vac; UL489)
25kA (600Vac; UL489)
25kA (600Y/347Vac; UL489)
20kA (250Vdc; UL489)
65kA (480Vac; UL489)
65kA (480Y/277Vac; UL489)
25kA (600Vac; UL489)
25kA (600Y/347Vac; UL489)
20kA (250Vdc; UL489)
Ultimate short circuit current breaking capacity (Icu)
100kA (220Vac/240Vac; IEC60947-2)
65kA (380Vac/400Vac/415Vac; IEC60947-2)
65kA (440Vac/480Vac; IEC60947-2)
25kA (500Vac/525Vac; IEC60947-2)
65kA (380Vac/400Vac/415Vac; IEC60947-2)
65kA (440Vac/480Vac; IEC60947-2)
25kA (500Vac/525Vac; IEC60947-2)
Service short circuit current breaking capacity (Ics)
100kA (220/240Vac; IEC60947-2)
65kA (380/415Vac; IEC60947-2)
65kA (440/480Vac; IEC60947-2)
25kA (500/525Vac; IEC60947-2)
65kA (380/415Vac; IEC60947-2)
65kA (440/480Vac; IEC60947-2)
25kA (500/525Vac; IEC60947-2)
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
100 %
Trip unit type
Technology = Thermal-Magnetic (adjustable)
Series = MCP (I)
Display = none
Series = MCP (I)
Display = none
Protection functions
I (Instantaneous protection)
Protection settings
Over-current -- fixed at 30A
I - Instantaneous protection against short-circuit -- adjustable 1...13 x ln (9A...325A)
I - Instantaneous protection against short-circuit -- adjustable 1...13 x ln (9A...325A)
Mounting mode
Mounts on I-line with line side isolated plug-on jaws + mechanical I-Line bracket mechanism for a robust attachment
Operating mode
Toggle (manual)
Degree of protection
IP40
Net Height (mm)
163 mm
Net Width (mm)
104 mm
Net Depth (mm)
86 mm
Utilisation category
A
Manufacturer product status
Commercialized
UPC code
785901675778
Compliant with standard(s)
EN / IEC (EU/Worldwide)
- CE marking
- EN/IEC 60947-2
United States of America
- UL Listed
- UL 489
- NEMA
Canada
- CSA C22.2 No 5
Mexico
- NOM
China
- CCC
Marine approvals
- ABS (American Bureau of Shipping)
- CE marking
- EN/IEC 60947-2
United States of America
- UL Listed
- UL 489
- NEMA
Canada
- CSA C22.2 No 5
Mexico
- NOM
China
- CCC
Marine approvals
- ABS (American Bureau of Shipping)
Benefits
A flexible high performance offer certified to global standards
Thermal magnetic or MicroLogic trip protection from 15-250A up to 600Vac and 250Vdc
2 and 3-pole unit mount and I-Line constructions
High performance UL listed interrupting ratings from 18 to 200kA at 480Vac
H- and J-Frame have common mounting holes handle locations and trim dimensions with many shared accessories and auxiliaries
UL/CSA/NOM/IEC/CCC certified and CE marked for global acceptance
Thermal magnetic or MicroLogic trip protection from 15-250A up to 600Vac and 250Vdc
2 and 3-pole unit mount and I-Line constructions
High performance UL listed interrupting ratings from 18 to 200kA at 480Vac
H- and J-Frame have common mounting holes handle locations and trim dimensions with many shared accessories and auxiliaries
UL/CSA/NOM/IEC/CCC certified and CE marked for global acceptance
Degree of pollution
3
Related Documents
Name | Last Update | Language |
---|---|---|
Schneider Electric 0100CT1501_SEC-03 - Digest Section 3 - Molded Case Circuit Breakers.pdf | 11 Mar 2019 | English (US) |
Schneider Electric 0100CT1501_SEC-07 - Digest Section 7 - Miniature and Molded Case Circuit Breakers.pdf | 11 Mar 2019 | English (US) |
Schneider Electric - PowerPacT MCCB-B-H-J-Q-frame - Catalogue.pdf | 31 Oct 2023 | English (US) |