Schneider Electric
HJL36030M71BCMotor circuit protector PowerPact H-Frame 3P 30A 600Vac/250Vdc 25kA lugs MCP (I) alarm sw. 80% rated
Motor circuit protector PowerPact H-Frame 3P 30A 600Vac/250Vdc 25kA lugs MCP (I) alarm sw. 80% rated
Electronic Motor Protector Circuit Breaker (MPCB) / Manual Motor Starter / Motor Circuit Protector (MCP) with factory-installed 1A/1B (1NO+1NC) alarm sw. - PowerPact H-Frame 150 MCP (I) 3P 30A 600Vac/250Vdc 25kA lugs - 80% rated - Square D by Schneider Electric - 3-poles (3P) - Rated current 30A - Short circuit breaking capacity 25kA (600Y/347Vac; UL489) - Thermal-Magnetic (adjustable) (MCP (I)) trip unit - Lugs on both load and line sides
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Brand
SKU
HJL36030M71BC
Online Price
$2,079.00
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
HJL36030M71BCSchneider Electric - PowerPact H-Frame - PowerPact HJL
Description
Electronic Motor Protector Circuit Breaker (MPCB) / Manual Motor Starter / Motor Circuit Protector (MCP) with factory-installed 1A/1B (1NO+1NC) alarm sw. - PowerPact H-Frame 150 MCP (I) 3P 30A 600Vac/250Vdc 25kA lugs - 80% rated - Square D by Schneider Electric - 3-poles (3P) - Rated current 30A - Short circuit breaking capacity 25kA (600Y/347Vac; UL489) - Thermal-Magnetic (adjustable) (MCP (I)) trip unit - Lugs on both load and line sides
Specifications
Primary brand
Square D by Schneider Electric
Main function
Motor Protection Circuit Breaker (MPCB)
Product series / family name
PowerPacT H-Frame motor protectors
Sub-range name
PowerPacT HJL
Functions
Electronic Motor Protector Circuit Breaker (MPCB) / Manual Motor Starter / Motor Circuit Protector (MCP)
Design
factory-installed 1A/1B (1NO+1NC) alarm sw.
PowerPact H-Frame 150 MCP (I) 3P 30A 600Vac/250Vdc 25kA lugs
80% rated
PowerPact H-Frame 150 MCP (I) 3P 30A 600Vac/250Vdc 25kA lugs
80% rated
Poles
3-poles (3P)
Rated current
30A
Trip current rating
30 AT
Frame current rating
150 AF
Rated operating voltage (Ue)
690 V
Rated Voltage (DC)
250Vdc
Rated voltage (AC)
600Y/347Vac
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
750 V
Connection type
Lugs on both load and line sides
Short circuit breaking rating
100kA (240Vac; UL489)
65kA (480Vac; UL489)
65kA (480Y/277Vac; UL489)
25kA (600Vac; UL489)
25kA (600Y/347Vac; UL489)
20kA (250Vdc; UL489)
65kA (480Vac; UL489)
65kA (480Y/277Vac; UL489)
25kA (600Vac; UL489)
25kA (600Y/347Vac; UL489)
20kA (250Vdc; UL489)
Ultimate short circuit current breaking capacity (Icu)
100kA (220Vac/240Vac; IEC60947-2)
65kA (380Vac/400Vac/415Vac; IEC60947-2)
65kA (440Vac/480Vac; IEC60947-2)
25kA (500Vac/525Vac; IEC60947-2)
65kA (380Vac/400Vac/415Vac; IEC60947-2)
65kA (440Vac/480Vac; IEC60947-2)
25kA (500Vac/525Vac; IEC60947-2)
Service short circuit current breaking capacity (Ics)
100kA (220/240Vac; IEC60947-2)
65kA (380/415Vac; IEC60947-2)
65kA (440/480Vac; IEC60947-2)
25kA (500/525Vac; IEC60947-2)
65kA (380/415Vac; IEC60947-2)
65kA (440/480Vac; IEC60947-2)
25kA (500/525Vac; IEC60947-2)
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
100 %
Trip unit type
Technology = Thermal-Magnetic (adjustable)
Series = MCP (I)
Display = none
Series = MCP (I)
Display = none
Protection functions
I (Instantaneous protection)
Protection settings
Over-current -- fixed at 30A
I - Instantaneous protection against short-circuit -- adjustable 1...13 x ln (9A...325A)
I - Instantaneous protection against short-circuit -- adjustable 1...13 x ln (9A...325A)
Mounting mode
Individual unit mount on plate
Operating mode
Toggle (manual)
Degree of protection
IP40
Net Height (mm)
163 mm
Net Width (mm)
104 mm
Net Depth (mm)
86 mm
Utilisation category
A
Manufacturer product status
Commercialized
Compliant with standard(s)
EN / IEC (EU/Worldwide)
- CE marking
- EN/IEC 60947-2
United States of America
- UL Listed
- UL 489
- NEMA
Canada
- CSA C22.2 No 5
Mexico
- NOM
China
- CCC
Marine approvals
- ABS (American Bureau of Shipping)
- CE marking
- EN/IEC 60947-2
United States of America
- UL Listed
- UL 489
- NEMA
Canada
- CSA C22.2 No 5
Mexico
- NOM
China
- CCC
Marine approvals
- ABS (American Bureau of Shipping)
Benefits
A flexible high performance offer certified to global standards
Thermal magnetic or MicroLogic trip protection from 15-250A up to 600Vac and 250Vdc
2 and 3-pole unit mount and I-Line constructions
High performance UL listed interrupting ratings from 18 to 200kA at 480Vac
H- and J-Frame have common mounting holes handle locations and trim dimensions with many shared accessories and auxiliaries
UL/CSA/NOM/IEC/CCC certified and CE marked for global acceptance
Thermal magnetic or MicroLogic trip protection from 15-250A up to 600Vac and 250Vdc
2 and 3-pole unit mount and I-Line constructions
High performance UL listed interrupting ratings from 18 to 200kA at 480Vac
H- and J-Frame have common mounting holes handle locations and trim dimensions with many shared accessories and auxiliaries
UL/CSA/NOM/IEC/CCC certified and CE marked for global acceptance
Degree of pollution
3
Related Documents
Name | Last Update | Language |
---|---|---|
Schneider Electric 0100CT1501_SEC-03 - Digest Section 3 - Molded Case Circuit Breakers.pdf | 11 Mar 2019 | English (US) |
Schneider Electric 0100CT1501_SEC-07 - Digest Section 7 - Miniature and Molded Case Circuit Breakers.pdf | 11 Mar 2019 | English (US) |
Schneider Electric - PowerPacT MCCB-B-H-J-Q-frame - Catalogue.pdf | 31 Oct 2023 | English (US) |