Schneider Electric
LGL37040D30Circuit breaker PowerPacT L-Frame 3P 40A 600Vac/500Vdc 20kA lugs 80% rated
Circuit breaker PowerPacT L-Frame 3P 40A 600Vac/500Vdc 20kA lugs 80% rated
Moulded Case Circuit Breaker (MCCB) - PowerPact L-Frame 600 TMD 3P 40A 600Vac/500Vdc 20kA lugs - 80% rated - UL listed 500Vdc - Square D by Schneider Electric - 3-poles (3P) - Rated current 40A - Short circuit breaking capacity 18kA (600Vac; UL489) - Thermal-Magnetic (adjustable) (TMD) trip unit - Lugs on both load and line sides
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Brand
SKU
LGL37040D30
Online Price
$6,950.00
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Schneider Electric - PowerPact L-Frame - PowerPact LGLLGL37040D30
Description
Moulded Case Circuit Breaker (MCCB) - PowerPact L-Frame 600 TMD 3P 40A 600Vac/500Vdc 20kA lugs - 80% rated - UL listed 500Vdc - Square D by Schneider Electric - 3-poles (3P) - Rated current 40A - Short circuit breaking capacity 18kA (600Vac; UL489) - Thermal-Magnetic (adjustable) (TMD) trip unit - Lugs on both load and line sides
Specifications
Primary brand
Square D by Schneider Electric
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
PowerPacT L-Frame complete breakers
Sub-range name
PowerPacT LGL
Functions
Moulded Case Circuit Breaker (MCCB)
Design
PowerPact L-Frame 600 TMD 3P 40A 600Vac/500Vdc 20kA lugs
80% rated
UL listed 500Vdc
80% rated
UL listed 500Vdc
Poles
3-poles (3P)
Rated current
40A
Trip current rating
40 AT
Frame current rating
600 AF
Rated operating voltage (Ue)
690 V
Rated Voltage (DC)
500Vdc
Rated voltage (AC)
600Vac
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
750 V
Connection type
Lugs on both load and line sides
Short circuit breaking rating
65kA (240Vac; UL489)
35kA (480Vac; UL489)
35kA (480Y/277Vac; UL489)
18kA (600Vac; UL489)
20kA (500Vdc; UL489)
35kA (480Vac; UL489)
35kA (480Y/277Vac; UL489)
18kA (600Vac; UL489)
20kA (500Vdc; UL489)
Ultimate short circuit current breaking capacity (Icu)
65kA (220Vac/240Vac; IEC60947-2)
18kA (380Vac/400Vac/415Vac; IEC60947-2)
18kA (440Vac/480Vac; IEC60947-2)
14kA (500Vac/525Vac; IEC60947-2)
18kA (380Vac/400Vac/415Vac; IEC60947-2)
18kA (440Vac/480Vac; IEC60947-2)
14kA (500Vac/525Vac; IEC60947-2)
Service short circuit current breaking capacity (Ics)
65kA (220/240Vac; IEC60947-2)
18kA (380/415Vac; IEC60947-2)
18kA (440/480Vac; IEC60947-2)
14kA (500/525Vac; IEC60947-2)
18kA (380/415Vac; IEC60947-2)
18kA (440/480Vac; IEC60947-2)
14kA (500/525Vac; IEC60947-2)
Trip unit type
Technology = Thermal-Magnetic (adjustable)
Series = TMD
Display = none
Series = TMD
Display = none
Protection functions
Thermal protection (Overload)
Magnetic protection (Short-circuit)
Magnetic protection (Short-circuit)
Protection settings
Over-current -- fixed at 40A
Short-circuit pickup current -- adjustable 1000A...2000A
Short-circuit pickup current -- adjustable 1000A...2000A
Mounting mode
Individual unit mount on plate
Operating mode
Toggle (manual)
Degree of protection
IP40
Net Height (mm)
382 mm
Net Width (mm)
153 mm
Net Depth (mm)
171 mm
Utilisation category
A
Manufacturer product status
Commercialized
Compliant with standard(s)
EN / IEC (EU/Worldwide)
- CE marking
- EN/IEC 60947-2
- EN/IEC 60947-5-1
United States of America
- UL Listed
- UL 489
- NEMA
Canada
- CSA C22.2 No 5
Mexico
- NOM
- NMX J-266
China
- CCC
Marine approvals
- ABS (American Bureau of Shipping)
- CE marking
- EN/IEC 60947-2
- EN/IEC 60947-5-1
United States of America
- UL Listed
- UL 489
- NEMA
Canada
- CSA C22.2 No 5
Mexico
- NOM
- NMX J-266
China
- CCC
Marine approvals
- ABS (American Bureau of Shipping)
Benefits
Basic Electronic and MicroLogic trip protection from 250-600Vac
2-pole 3-pole and 4-pole design wide range of trip units to protect most applications
High performance UL listed interrupting ratings from 35kA to 200kA at 480Vac
Standard (80%) or 100% rating
UL/CSA/NOM/IEC/CCC certified and CE marked for global acceptance
2-pole 3-pole and 4-pole design wide range of trip units to protect most applications
High performance UL listed interrupting ratings from 35kA to 200kA at 480Vac
Standard (80%) or 100% rating
UL/CSA/NOM/IEC/CCC certified and CE marked for global acceptance
Degree of pollution
3
Related Documents
Name | Last Update | Language |
---|---|---|
Download official PDF datasheet for LGL37040D30 from Schneider Electric | 18 Jun 2021 | English (US) |
Schneider Electric 0100CT1501_SEC-03 - Digest Section 3 - Molded Case Circuit Breakers.pdf | 11 Mar 2019 | English (US) |
Schneider Electric 0100CT1501_SEC-07 - Digest Section 7 - Miniature and Molded Case Circuit Breakers.pdf | 11 Mar 2019 | English (US) |
Schneider Electric - PowerPacT MCCB-B-H-J-Q-frame - Catalogue.pdf | 31 Oct 2023 | English (US) |