Schneider Electric
LJL36600M38XMotor circuit protector PowerPact L-Frame 3P 600A 600Vac 25kA lugs Micrologic 2.2M 80% rated
Motor circuit protector PowerPact L-Frame 3P 600A 600Vac 25kA lugs Micrologic 2.2M 80% rated
Electronic Motor Protector Circuit Breaker (MPCB) / Manual Motor Starter / Motor Circuit Protector (MCP) - PowerPact L-Frame 600 Micrologic 2.3M (LSI) 3P 600A 600Vac 25kA lugs - 80% rated - Square D by Schneider Electric - 3-poles (3P) - Rated current 600A (line rated current) - Rated voltage 600Vac - Short circuit breaking capacity 25kA (600Y/347Vac; UL489) - Electronic (Micrologic 2.3M (LSI)) trip unit - Lugs on both load and line sides
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Brand
SKU
LJL36600M38X
Online Price
$8,604.00
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Schneider Electric - PowerPact L-Frame - PowerPact LJLLJL36600M38X
Description
Electronic Motor Protector Circuit Breaker (MPCB) / Manual Motor Starter / Motor Circuit Protector (MCP) - PowerPact L-Frame 600 Micrologic 2.3M (LSI) 3P 600A 600Vac 25kA lugs - 80% rated - Square D by Schneider Electric - 3-poles (3P) - Rated current 600A (line rated current) - Rated voltage 600Vac - Short circuit breaking capacity 25kA (600Y/347Vac; UL489) - Electronic (Micrologic 2.3M (LSI)) trip unit - Lugs on both load and line sides
Specifications
Primary brand
Square D by Schneider Electric
Main function
Motor Protection Circuit Breaker (MPCB)
Product series / family name
PowerPacT L-Frame motor protectors
Sub-range name
PowerPacT LJL
Functions
Electronic Motor Protector Circuit Breaker (MPCB) / Manual Motor Starter / Motor Circuit Protector (MCP)
Design
PowerPact L-Frame 600 Micrologic 2.3M (LSI) 3P 600A 600Vac 25kA lugs
80% rated
80% rated
Poles
3-poles (3P)
Rated current
600A (line rated current)
520A FLA (Full Load Amperes)
520A FLA (Full Load Amperes)
Trip current rating
600 AT
Frame current rating
600 AF
Rated operating voltage (Ue)
690 V
Rated Voltage (DC)
250Vdc
Rated voltage (AC)
600Vac
600Y/347Vac
600Y/347Vac
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
750 V
Connection type
Lugs on both load and line sides
Short circuit breaking rating
100kA (240Vac; UL489)
65kA (480Vac; UL489)
65kA (480Y/277Vac; UL489)
25kA (600Vac; UL489)
25kA (600Y/347Vac; UL489)
65kA (480Vac; UL489)
65kA (480Y/277Vac; UL489)
25kA (600Vac; UL489)
25kA (600Y/347Vac; UL489)
Ultimate short circuit current breaking capacity (Icu)
100kA (220Vac/240Vac; IEC60947-2)
65kA (380Vac/400Vac/415Vac; IEC60947-2)
65kA (440Vac/480Vac; IEC60947-2)
25kA (500Vac/525Vac; IEC60947-2)
65kA (380Vac/400Vac/415Vac; IEC60947-2)
65kA (440Vac/480Vac; IEC60947-2)
25kA (500Vac/525Vac; IEC60947-2)
Service short circuit current breaking capacity (Ics)
100kA (220/240Vac; IEC60947-2)
65kA (380/415Vac; IEC60947-2)
65kA (440/480Vac; IEC60947-2)
25kA (500/525Vac; IEC60947-2)
65kA (380/415Vac; IEC60947-2)
65kA (440/480Vac; IEC60947-2)
25kA (500/525Vac; IEC60947-2)
Trip unit type
Technology = Electronic
Series = Micrologic 2.3M (LSI)
Protection = LSI
Display = none
Series = Micrologic 2.3M (LSI)
Protection = LSI
Display = none
Protection functions
L (Long-time protection)
S (Short-time protection with fixed time delay)
I (Instantaneous protection)
S (Short-time protection with fixed time delay)
I (Instantaneous protection)
Protection settings
L - Protection against overload -- adjustable 0.6...1 x In (FLA 312A...520A)
S - Protection against short-circuit with time delay -- adjustable 5...13 x FLA (1560A...6760A)
I - Instantaneous protection against short-circuit -- fixed at 7200A
(Phase unbalance or phase loss) trip >30% unbalance; time delay 0.7s during starting; 4s during normal operation
S - Protection against short-circuit with time delay -- adjustable 5...13 x FLA (1560A...6760A)
I - Instantaneous protection against short-circuit -- fixed at 7200A
(Phase unbalance or phase loss) trip >30% unbalance; time delay 0.7s during starting; 4s during normal operation
Mounting mode
Individual unit mount on plate
Operating mode
Toggle (manual)
Degree of protection
IP40
Net Height (mm)
382 mm
Net Width (mm)
153 mm
Net Depth (mm)
171 mm
Utilisation category
A
Manufacturer product status
Commercialized
Compliant with standard(s)
EN / IEC (EU/Worldwide)
- CE marking
- EN/IEC 60947-2
United States of America
- UL Listed
- UL 489
- NEMA
Canada
- CSA C22.2 No 5
Mexico
- NOM
China
- CCC
Marine approvals
- ABS (American Bureau of Shipping)
- CE marking
- EN/IEC 60947-2
United States of America
- UL Listed
- UL 489
- NEMA
Canada
- CSA C22.2 No 5
Mexico
- NOM
China
- CCC
Marine approvals
- ABS (American Bureau of Shipping)
Benefits
Basic Electronic and MicroLogic trip protection from 250-600Vac
2-pole 3-pole and 4-pole design wide range of trip units to protect most applications
High performance UL listed interrupting ratings from 35kA to 200kA at 480Vac
Standard (80%) or 100% rating
UL/CSA/NOM/IEC/CCC certified and CE marked for global acceptance
2-pole 3-pole and 4-pole design wide range of trip units to protect most applications
High performance UL listed interrupting ratings from 35kA to 200kA at 480Vac
Standard (80%) or 100% rating
UL/CSA/NOM/IEC/CCC certified and CE marked for global acceptance
Degree of pollution
3
Related Documents
Name | Last Update | Language |
---|---|---|
Download official PDF datasheet for LJL36600M38X from Schneider Electric | 18 Jun 2021 | English (US) |
Schneider Electric 0100CT1501_SEC-03 - Digest Section 3 - Molded Case Circuit Breakers.pdf | 11 Mar 2019 | English (US) |
Schneider Electric 0100CT1501_SEC-07 - Digest Section 7 - Miniature and Molded Case Circuit Breakers.pdf | 11 Mar 2019 | English (US) |
Schneider Electric - PowerPacT MCCB-B-H-J-Q-frame - Catalogue.pdf | 31 Oct 2023 | English (US) |