Specifications
Primary brand
Eaton
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
LZM4-4
Network frequency
50/60 Hz
Functions
Molded/Moulded Case Circuit Breaker (MCCB)
Rated current
1000A
Trip current rating
1000 AT
Frame current rating
1600 AF
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
1000 V
Connection type
Lugs
Poles
4 Pole(s)
Protected poles
4 Pole(s)
Ultimate short circuit current breaking capacity (Icu)
125kA (240Vac)
85kA (415Vac)
85kA (440Vac)
65kA (525Vac)
50kA (690Vac)
85kA (415Vac)
85kA (440Vac)
65kA (525Vac)
50kA (690Vac)
Service short circuit current breaking capacity (Ics)
43kA (415Vac)
43kA (440Vac)
49kA (525Vac)
37kA (690Vac)
43kA (440Vac)
49kA (525Vac)
37kA (690Vac)
Trip unit type
Electronic (selective + generator protection) (LSI)
Protection functions
L (Long-time protection)
S (Short-time protection with fixed time delay)
I (Instantaneous protection)
S (Short-time protection with fixed time delay)
I (Instantaneous protection)
Protection settings
L (Long-time protection) adjustable 500-1000A
S (Short-time protection with fixed time delay) adjustable 1000-10000A
I (Instantaneous protection) adjustable 2000-12000A
S (Short-time protection with fixed time delay) adjustable 1000-10000A
I (Instantaneous protection) adjustable 2000-12000A
Operating mode
Toggle
Electrical durability (with load)
10 000 operations
Service short circuit current breaking capacity (Ics)
63kA (240Vac) kA
Order code / Manufacturer SKU
110994
Manufacturer product status
Commercialized
Rated voltage (AC)
690 V
Compliant with standard(s)
IEC/EN 60947
Degree of pollution
3