Schneider Electric
METSEPM8240
Digital Power Meter - Schneider Electric (PM8000 series) - PM8240 powermeter - meter - 3DI / 1 pulse outputDO - Colour TFT LCD display - Up to the 63rd harmonic
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
Brand
SKU
METSEPM8240
Online Price
$9,306.61
Please add this item to cart to request a quote or contact us at sales@lakelandengineering.com for product availability.
PowerLogic
Description
Digital Power Meter - Schneider Electric (PM8000 series) - PM8240 powermeter - meter - 3DI / 1 pulse outputDO - Colour TFT LCD display - Up to the 63rd harmonic
Specifications
Primary brand
Schneider Electric
Secondary brand
Merlin Gerin
Product series / family name
PowerLogic
Sub-range name
PM8000
Network frequency
42-69 Hz
Functions
Ethernet
Type of network
1P + N
3P
3P + N
3P
3P + N
Sampling rate
(256 samples/cycle; 42Hz) 10 752 Hz
(256 samples/cycle; 69Hz) 17 664 Hz
(256 samples/cycle; 69Hz) 17 664 Hz
Memory capacity
512 MB
Communication protocol
Modbus RTU
Ethernet (Modbus TCP/IP daisy chain
(ION 2-wire) 115 kbauds
RSTP 801.1d
DNP3
IEC 61850
Ethernet (Modbus TCP/IP daisy chain
(ION 2-wire) 115 kbauds
RSTP 801.1d
DNP3
IEC 61850
Measurement accuracy
0.1% current
0.1% voltage
0.2% active energy
0.1% voltage
0.2% active energy
Degree of protection
IP30 (body)
IP54 (front)
IP54 (front)
Net Height (mm)
96 mm
Net Width (mm)
96 mm
Net Depth (mm)
77.5 mm
Ambient air temperature for operation
-25/+70 °C
Display type
Colour TFT LCD
Power consumption
18-36 VA
(CT burden at 10A) 0.024 VA
(CT burden at 10A) 0.024 VA
Contacts type
(Digital outputs) SPDT (Single Pole Double Throw)
Secondary current
(CT secondary current) 1 A
(CT secondary current) 5 A
(CT secondary current) 5 A
Resistance
(VT input impedance) 5M Ω
(Current input impedance) 0.3milli Ω
(Current input impedance) 0.3milli Ω
Compliant with standard(s)
IEC61010-1
IEC62052-11
IEC61557-12
IEC62053-22
IEC62053-24
IEC61000-4-11
IEC61000-4-8
IEC61000-4-6
IEC61000-4-5
IEC61000-4-4
IEC61000-4-3
IEC61000-4-2
FCC part 15 Class A
UL61010-1
CULus conforming to CSA C22.2 No 61010-1
CLC/TR50579
IEC62052-11
IEC61557-12
IEC62053-22
IEC62053-24
IEC61000-4-11
IEC61000-4-8
IEC61000-4-6
IEC61000-4-5
IEC61000-4-4
IEC61000-4-3
IEC61000-4-2
FCC part 15 Class A
UL61010-1
CULus conforming to CSA C22.2 No 61010-1
CLC/TR50579
Mounting mode
Flush mounting
Degree of pollution
2
Measurement function
Power factor (Total / per phase)
Frequency
Voltage
Current
Accumulated Active; Reactive and Apparent Energy
Demand predicted active; reactive; apparent power
Demand active; reactive; apparent power (Present; max. values)
Demand current average (Present; max. values)
Real/active power (Total or per-phase)
Reactive power (Total or per-phase)
Apparent power (Total or per-phase; signed or four-quadrant)
Up to the 63rd harmonic
Synchronization of the measurement window
Demand setting of calculation (Block; sliding)
Frequency
Voltage
Current
Accumulated Active; Reactive and Apparent Energy
Demand predicted active; reactive; apparent power
Demand active; reactive; apparent power (Present; max. values)
Demand current average (Present; max. values)
Real/active power (Total or per-phase)
Reactive power (Total or per-phase)
Apparent power (Total or per-phase; signed or four-quadrant)
Up to the 63rd harmonic
Synchronization of the measurement window
Demand setting of calculation (Block; sliding)
Accuracy class
Class 0.2S (active energy according to IEC 62053-22)
Class 0.2 (active energy according to ANSI C12.20)
Class 0.5S (reactive energy according to IEC 62053-24)
Class 0.2 (current according to IEC 61557-12)
Class 0.2 (voltage according to IEC 61557-12)
Class 0.2 (active power according to IEC 61557-12)
Class 0.5 (power factor according to IEC 61557-12)
Class 0.2 (active energy according to ANSI C12.20)
Class 0.5S (reactive energy according to IEC 62053-24)
Class 0.2 (current according to IEC 61557-12)
Class 0.2 (voltage according to IEC 61557-12)
Class 0.2 (active power according to IEC 61557-12)
Class 0.5 (power factor according to IEC 61557-12)
Data recording
Time stamping
(Data recording) Min/max of instantaneous values
Min/max of instantaneous values
Sequence of event recording
GPS synchronisation
Event logs
Data logs
Sag and swell logs
Harmonics logs
Waveform logs
Trending/forecasting
(Data recording) Min/max of instantaneous values
Min/max of instantaneous values
Sequence of event recording
GPS synchronisation
Event logs
Data logs
Sag and swell logs
Harmonics logs
Waveform logs
Trending/forecasting
Related Documents
Name | Last Update | Language |
---|---|---|
Schneider Electric - PowerLogic digital meter & systems - Catalogue.pdf | 31 Aug 2018 | English (US) |